Dent – Building Sub-Metering

ELITEproXCPowerScout 3037PowerScout 12 HDPowerScout 48 HD

Typical Applications/Usage

Measurement and Verification (M&V) studies, electrical load profiling, energy audits, new technology assessment studies. The ELITEpro XC is typically installed inside an electrical panel for a finite period of time (weeks to months).

Tenant submetering (shopping malls, apartments, office spaces, etc), net metering, data center monitoring or other commercial/industrial applications. The PowerScout 3037 is not meant to be a stand alone energy recorder. They are designed to connect as a slave device to a data logger, Remote Terminal Unit (RTU), or building management host network.

Tenant submetering (shopping malls, apartments, office spaces, etc), net metering, data center monitoring or other commercial/industrial applications. The PowerScout 12 HD is not meant to be a stand alone energy recorder. They are designed to connect as a slave device to a data logger, Remote Terminal Unit (RTU), or building management host network.

Tenant submetering (shopping malls, apartments, office spaces, etc), net metering, data center monitoring or other commercial/industrial applications. The PowerScout 48 HD is not meant to be a stand alone energy recorder. They are designed to connect as a slave device to a data logger, Remote Terminal Unit (RTU), or building management host network.

Service Types

Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta), DC Systems (Solar/Battery)

Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta)

Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta)

Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta)

Voltage Channels

3 channels, CAT III, 0-600 VAC (line-to-line) or 600 VDC

80-346 Volts AC Line-to-Neutral, 600V Line-to-Line, CAT III.

90-346 Volts AC Line-to-Neutral, 600V Line-to-Line, CAT III.

90-346 Volts AC Line-to-Neutral, 600V Line-to-Line, CAT III. Two voltage reference inputs.

Current Channels

4 channels, .67 VAC max, +/- 1 VDC. Ideal for 333 mV full scale CTs

3 channels, 0.525 VAC max, 333 mV CTs, 0-4,000+ Amps depending on CT

12 channels, 0.525 VAC max, 333 mV CTs, 0-4,000 Amps depending on CT

48 channels, 0.525 VAC max, 333 mV CTs, 0-4,000 Amps depending on CT

Maximum Current Input

External transducer dependent.
200% of current transducer rating (mV CTs)
Measure up to 6000A with RoCoil CTs.

158% of current transducer rating (mV CTs) to maintain accuracy.
Measure up to 4000A with RōCoil CTs

150% of current transducer rating (mV CTs) to maintain accuracy. Measure up to 4000A with RōCoil CTs

150% of current transducer rating (mV CTs) to maintain accuracy. Measure up to 4000A with RōCoil CTs

Analog Channels

4 channels, 0-10 Volts, 0-20 or 4-20 mA current loop. Non-isolated, external power for current loop. User scaling for sensor reporting in physical units.

N/A

N/A

N/A

Measurement Type

True RMS using high-speed digital signal processing (DSP)

True RMS using high-speed digital signal processing (DSP)

True RMS using high-speed digital signal processing (DSP) with continuous sampling

True RMS using high-speed digital signal processing (DSP) with continuous sampling

On Board Memory

16 MB non-volatile. Depending on the setup table, any measurement can be recorded at the integration period with a time stamp.

N/A

Energy (kWh) values are recorded every 15 minutes for 63 days (downloadable log) Each record is time stamped

Energy (kWh) values are recorded every 15 minutes for 63 days (downloadable log) Each record is time stamped

Line Frequency

DC/50/60 Hz

50/60 Hz

50/60 Hz (45-70 Hz measurable range). Measurement taken L1-N.

50/60 Hz (45-70 Hz measurable range). Measurement taken L1-N.

Waveform Sampling

12 kHz
200 samples/cycle at 60Hz
240 samples/cycle at 50Hz

12 kHz

1.8 kHz

1.8 kHz

Parameter Update Rate

8 Hz or every 125 mSec.

0.5 seconds

1 second

1 second

Blind Cycles

8 Hz or every 125 mSec.

0.5 seconds

None

None

Integration Period

1, 3, 15, 30 seconds; 1, 2, 5, 10, 15, 20, and 30 minutes; 1 and 12 hours, 1 day

N/A

15 minutes

15 minutes

Energy Measurements

Volts, Amps, Amp-Hrs (Ah), kW, kWh, kVAR, kVARh, kVA, kVAh, Displacement Power Factor (dPF). All parameters for each phase and for system total.

Volts, Amps, kW, kVAR, kVARh, kVA, kVAh, aPF, dPF, kW demand, kVA demand, Import (Received) kWh, Export (Delivered) kWh, Import (Received) kVAh, Export (Delivered) kVAh, Import (Received) kVARh, Export (Delivered) kVARh, Frequency. All parameters for each phase and system total.

Volts, Amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, Import (Received) kWh, Export (Delivered) kWh, Net kWh, Import (Received) kVAh, Export (Delivered) kVAh, Net kVAh, Import (Received) kVARh, Export (Delivered) kVARh, Net kVARh, THD, Theta, Frequency. All parameters for each phase and element total.

Volts, Amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, Import (Received) kWh, Export (Delivered) kWh, Net kWh, Import (Received) kVAh, Export (Delivered) kVAh, Net kVAh, Import (Received) kVARh, Export (Delivered) kVARh, Net kVARh, THD, Theta, Frequency. All parameters for each phase and element total.

Accuracy

Better than 1% (<0.2% typical) for V, A, kW, kVAR, kVA, PF, Analog

0.2% ANSI C12.20-2010 Class 0.2

0.2% ANSI C12.20-2010 Class 0.2

0.2% ANSI C12.20-2010 Class 0.2

Resolution

0.01 Amp, 0.001 Volt, 1 Watt, 1 VAR, 1 VA, 0.01 PF, 0.001 Analog

0.01 Amp, 0.1 Volt, 0.01 Watt, 0.01 VAR, 0.01 VA, 0.01 Power Factor depending on scalar setting

Values in IEEE-754 single precision floating point format (32 bit).

Values in IEEE-754 single precision floating point format (32 bit).

LED Indicators

Tri-color (red, green, blue): 1 LED indicates communication (blue for wireless, Bluetooth® or Ethernet), 4 LEDs for correct phasing (PhaseChek™).

Communications, pulse output, and PhaseChek™

N/A

N/A

Display

None

Optional 2 x 16 character display which auto-cycles between screens; real-time values updated every second

Optional 4-line display, tri-color backlight (PhaseChek™)

Optional 4-line display, tri-color backlight (PhaseChek™)

Line Power

From L1 Phase to L2 Phase. 80-600V (AC or DC) CAT III DC/50/60 Hz, 125 mA, 5 W, or 10 VA max. Non-user replaceable .5 Amp internal fuse protection.

From L1 Phase to L2 Phase. 80-600VAC CAT III 50/60Hz, 90mA Max. Non-user replaceable .5 Amp internal fuse protection

From L1 Phase to L2 Phase. 90-600VAC RMS CAT III 50/60Hz, 500mA AC Max. Use of 12 volt auxiliary output requires 100 VAC minimum input voltage.

From L1 Phase to L2 Phase. 90-600VAC RMS CAT III 50/60Hz, 500mA AC Max. Use of 12 volt auxiliary output requires 100 VAC minimum input voltage.

Auxiliary Power In

6-10 VDC, 500 mA

USB

USB

USB

Power Out

6 VDC, 200 mA max

Unregulated 5VDC output, 140 mA max

Unregulated 12VDC output, 200 mA, self-resetting fuse.

Unregulated 12VDC output, 200 mA, self-resetting fuse.

Pulse Output

N/A

Open Collector, optically isolated, 5mA max current, 30V max open voltage

N/A

N/A

Pulse Input

N/A

N/A

Four inputs. 3.3V sourcing voltage (current limited) to customer dry contact pulse output. Max pulse rate 10 Hz (50 mSec minimum transition time).

Two inputs. 3.3V sourcing voltage (current limited) to customer dry contact pulse output. Max pulse rate 10 Hz (50 mSec minimum transition time).

Alarm Output

N/A

N/A

Over/Under Voltage & Current (SPDT Relay - 30 VDC)

Over/Under Voltage & Current (SPDT Relay - 30 VDC)

USB

USB standard (Type B). 1.8 M (6 ft) A-to-B USB Cable (included)

USB standard (Type B). For configuration only.

USB standard (Type B). For configuration only or downloading of logged data.

USB standard (Type B). For configuration only or downloading of logged data.

Ethernet

Standard Ethernet. Configure for DHCP or Static IP.

Optional Ethernet. Configure for DHCP or Static IP.

Standard Ethernet. Configure for DHCP or Static IP.

Standard Ethernet. Configure for DHCP or Static IP.

Bluetooth

Optional. Internal antenna with 10-100 ft range (typical). Requires Bluetooth® wireless technology adapter on Windows PC. Adapter must support the Serial Port Profile (SPP).

N/A

N/A

N/A

Wi-Fi

Optional. Wi-Fi option available as two separate configurations:
• Internal antenna: typical range 75-300 ft.
• External 3 dbi antenna: typical range 150-300 ft.

N/A

N/A

N/A

Modbus

N/A

Modbus RTU (RS-485) or Modbus TCP

Modbus RTU (RS-485) or Modbus TCP

Modbus RTU (RS-485) or Modbus TCP

BACnet

N/A

BACnet MS/TP (RS-485) or BACnet IPBACnet MS/TP (RS-485) or BACnet IP

BACnet MS/TP (RS-485) or BACnet IP

BACnet MS/TP (RS-485) or BACnet IP

Supported Baud Rates

N/A

Modbus: 9600 (Default), 19200, 38400, 57600, 76800, 115200 baud
BACnet: 9600, 19200, 38400, 57600, 76800 (Default), 115200

9600 (Default), 19200, 38400, 57600, 76800, 115200

9600 (Default), 19200, 38400, 57600, 76800, 115200

Operating Temperature

-7 to + 60 °C (20 to 140 °F)

-7° to 60°C (-20° to 140°F)

-20° to 60°C (-4° to 140°F)

-20° to 60°C (-4° to 140°F)

Operating Humidity

5% to 95% non-condensing

5% to 95% non-condensing

5% to 95% non-condensing

5% to 95% non-condensing

Enclosure Type

ABS plastic, 94-V0 flammability rating

ABS Plastic, 94-V0 flammability rating

ABS Plastic, 94-V0 flammability rating. Connections: 1” EMT conduit

ABS Plastic, 94-V0 flammability rating. Connections: 1” EMT conduit

Circuit Board Only Option

N/A

N/A

Circuit board on mounting plate available

Circuit board on mounting plate available

Weight

340 g (12 ounces)

340 g (12 ounces)

1043 g - 1452 g (2.3 - 3.2 lbs) depending on configuration

1814 g - 2223 g (4.0 - 4.9 lbs) depending on configuration

Dimensions

(L) 21.6 cm x (W) 6.3 cm x (H) 4.7 cm (8.5” x 2.5” x 1.9”)

(L) 24.2 cm x (W) 8.5 cm x (H) 4.0 cm (9.5” x 3.3” x 1.6”)

Enclosure: (L) 24.8cm x (W) 25.1cm x (H) 8.0 cm (9.8” x 9.8” x 3.1”)
Mounting Plate: (L) 17.8cm x (W) 26.3cm x (H) 8.0 cm (7.0” x 10.4” x 3.1”)

Enclosure: (L) 33.7cm x (W) 25.1cm x (H) 8.0 cm (13.3” x 9.8” x 3.1”)
Mounting Plate: (L) 26.2cm x (W) 24.1cm x (H) 8.0 cm (10.3” x 9.5” x 3.1”)

Mounting Options

Mounting tabs or magnets

Mounting tabs or TS35/7 DIN Rail

Panel Mount/Enclosure

Panel Mount/Enclosure

UL

UL Listed- Conforms to UL Std 61010-1
Certified to CSA Std C22.2 No. 61010-1

UL Listed- Conforms to UL Std 61010-1, 3rd Edition & IEC 61010-2-030 1st edition

Circuit Board on Plate: UL Recognized-Conforms to UL Std 61010-1 3rd Edition
Certified to CSA Std C22.2 No. 61010-1 3rd Edition
Enclosure Version: UL Listed-Conforms to UL Std 61010-1 3rd Edition
Certified to CSA Std C22.2 No. 61010-1 3rd Edition

Circuit Board on Plate: UL Recognized- Conforms to UL Std 61010-1 3rd Edition
Certified to CSA Std C22.2 No. 61010-1 3rd Edition
Enclosure Version: UL Listed- Conforms to UL Std 61010-1 3rd Edition
Certified to CSA Std C22.2 No. 61010-1 3rd Edition

CE

EN 61000-6-4: Class A

EN 61000-6-4: Class A

EN 61000-6-4: Class A

EN 61000-6-4: Class A

ANSI C12.20 Class 0.2

N/A

NIST Traceable Calibration

NIST Traceable Calibration

NIST Traceable Calibration