Dent – Split Core CTs

Part Name/NumberWindow SizeOutput SignalUseful Current RangeNominal RatingAccuracyDimensionsWeightOutput LeadSafety RequirementsWorking Voltage

High Performance Mini Hinged CTs
CT-HSC-020, -050

1 cm (0.4”)333 mV at rated current0.25-40 Amps 0.25-80 Amps20, 50 Amps<0.5% at rated current2.6 x 2.9 x 4.2 cm (1.04 x 1.16” x 1.64”)91 g (3.2 oz)Leads 2.7 m (8 ft) twisted pair, 20 AWGUL Recognized: UL STD 61010-1 Certified to: CAN/CSA STD C22.2 No. 61010-1Maximum 600 Vrms Category III

High Performance Midi Hinged CTs
CT-HMC-100, -200

2.5 cm (1.0”)333 mV at rated current1-200 Amps 1-300 Amps100, 200 Amps<1.0% at rated current4.7 x 4.7 x 7.0 cm (1.85 x 1.85 x 2.76”)221 g (7.8 oz)Leads 2.7 m (8 ft) twisted pair, 22 AWGUL Recognized: UL STD 61010-1 Certified to: CAN/CSA STD C22.2 No. 61010-1Maximum 600 Vrms Category III

Split Core Current Transformers
CT-SCS-0050, -0100

1.9 cm (.75”)333 mV at rated current1-65, 2-130 Amps50, 100 Amps+/- 1% at 10% to 130% of rated current5.08 x 5.34 x 1.55 cm (2.0 x 2.1 x 0.6”)136 g (4.8 oz)Leads 2.7 m (8 ft) twisted pair, 20 AWGConforms to UL STD 61010-1 Certified to CAN/CSA STD C22.2 No. 61010Maximum 600 Vrms Category III

Split Core Current Transformers
CT-SCM-0100, -0200, -0400, -0600

3.2 cm (1.25”)333 mV at rated current5-130, 4-260, 8-520, 12-780 Amps100, 200, 400, 600 Amps+/- 1% at 10% to 130% of rated current8.26 x 8.6 x 2.54 cm (3.3 x 3.4 x 1.0”)340 g (12 oz)Leads 2.7 m (8 ft) twisted pair, 20 AWGConforms to UL STD 61010-1 Certified to CAN/CSA STD C22.2 No. 61010Maximum 600 Vrms Category III